up to 4kW 1Ph-230V, K2000 series - KLINGER BORN

Skip Navigation

Choose language

Sie befinden sich hier: Products » Starters » Switch-Plug-Combinations » up to 4kW 1Ph-230V, K2000 series » Example combinations

Caption

  • Description of the below used symbols:
  • versions
  • dimensions
  • examples
  • options
  • send request

Example combinations Series K2000 - up to 4.0 kW 1 phase 230 V


Please note that all our switches are custom-made. Because of the numerous ways the individual components can be combined, we can offer a high number of different models. For the same reason, there are no switches available on stock. The following combinations merely illustrate the wide range of possibilities, they are not available on stock. Delivery time on enquiry.


K2000 / ST6 / KA12
Model-No.: 0098.2000

K2000, Mod.No. 0098.2000
Circuit diagram 0098.2000

Technical data:

Undervoltage trigger
Without
Switching capacity
4.0 kW 230 V~/AC-3
Ie
16.0 A
Plug
Earthing-pin plug 2P+E 16A according to CEE7/VII
Motor connecting lead
1 mtr. H07RN-F 3G 1.5
Protection type
IP54
Fixing dimensions
68 x 68 mm
Case color
Yellow
Plug color
Blue

K2000 / ST6 / KA12 / Therm
Model-No.: 0098.2010

K2000, Mod.No. 0098.2010
Circuit diagram 0098.2010

Technical data:

Undervoltage trigger
Uc: 230 V/50 Hz
Switching capacity
4.0 kW 230 V~/AC-3
Ie
16.0 A
Plug
Earthing-pin plug 2P+E 16A according to CEE7/VII
Motor connecting lead
1 mtr. H07RN-F 5G 1.5 with facility for connecting a thermistor contact
Protection type
IP54
Fixing dimensions
68 x 68 mm
Case color
Yellow
Plug color
Blue

K2000 / NKA6 / KA6 / Therm
Model-No.: 0098.2020

K2000, Mod.No. 0098.2020
Circuit diagram 0098.2020

Technical data:

Undervoltage trigger
Uc: 230 V/50 Hz
Switching capacity
4.0 kW 230 V~/AC-3
Ie
16.0 A
Mains lead:
2 mtr. H07RN-F 3G 1.5 with Schuko-plug
Connecting lead
1 mtr. H07RN-F 5G 1.5 with facility for connecting a thermistor contact
Protection type
IP54
Fixing dimensions
68 x 68 mm
Case color
Yellow

K2000 / ST6 / KA12 / Mx,xA
Model-No.: 0098.2030

K2000, Mod.No. 0098.2030
Circuit diagram 0098.2030

Technical data:

Undervoltage trigger
Uc: 230 V/50 Hz
Switching capacity
4.0 kW 230 V~/AC-3
Ie
16.0 A
Plug
Earthing-pin plug 2P+E 16A according to CEE7/VII
Overload protection
Typ KB-SM-30, see option overload protection
Connecting lead
1 mtr. H07RN-F 3G 1.5
Protection type
IP54
Fixing dimensions
68 x 68mm
Case color
Yellow
Plug color
Blue

Please specify rated motor current !!!
Model-No.: 0098.2030 M....,..A


Terminal leads are stripped to a length of 100mm and fitted with connector sleeves.