Thermic Overload relais for contactor KLIBO7,5 - KLINGER BORN

Skip Navigation

Choose language

Sie befinden sich hier: Products » Contactors » Thermic Overload relais for contactor KLIBO7,5

Thermic Overload relais for contactor KLIBO7,5

according to IEC/EN 60947-4-1

Thermic Overload relais TA25DU

Special features:

  • 3-pole
  • Can be set to automatic or manual reset
  • Reset button with switch-off functionality (test)
  • 2 auxiliary switches with galvanic isolation (NO and NC)
  • With temperature compensation
  • With phase drop-out sensitivity

Technical data:

Designation
TA25DU
Rated operational voltage Ue
690 V
Withstand voltage Uimp
6 kV
Permissible ambient temperature
-40 °C ... +70 °C = Storage temperature
-25 °C ... +55 °C = Operating temperature
Mounting position
Any
Mounting
Hook into contactor, tighten screws of main terminals
Connecting terminals
Screw terminals
Terminal cross-section
2x 1.5-4 mm² (finely stranded with ferrules)
2x 0.75-2.5 mm² (finely straded with ferrules - auxiliary contacts)
Adjustement range
see versions and article numbers
Tripping class
10 A
Frequency range
0 ... 400 Hz
Switching capacity
Up to 15 switching operations per hour or up to 60 switching operations per hour at 40%

Technical data of auxiliary contacts:

Auxiliary contacts 95-96
Break contact, when thermically triggered
Auxiliary contacts 97-98
Make contact, when thermically triggered
Rated operational voltage
500 V
Conventional thermical continuous current Ith
6 A
Rated operational current Ie
At AC15 up to 240 V 1.5 A
At AC15 up to 440 V 0.7 A
At AC15 up to 500 V 0.5 A
Short-circuit protection gG
4 A

Use in series


Versions:

Art.No. from/till Short-circuit protection Resistance
per phase
Power loss per phase with current set to upper limit
gG S223K
40367048 1.0 - 1.4 A 4 A 1.6 A 1120 mΩ 2.2 W
40367049 1.3 - 1.8 A 6 A 2 A 670 mΩ 2.2 W
40367050 1.7 - 2.4A 6 A 3 A 383 mΩ 2.2 W
40367051 2.2 - 3.1A 10 A 3 A 229 mΩ 2.2 W
40367052 2.8 - 4.0 A 10 A 4 A 137 mΩ 2.2 W
40367053 3.5 - 5.0 A 16 A 6 A 87.5 mΩ 2.2 W
40367054 4.5 - 6.5 A 20 A 8 A 51 mΩ 2.2 W
40367055 6.0 - 8.5 A 25 A 10 A 30.4 mΩ 2.2 W
40367056 7.5 - 11 A 35 A 16 A 18.2 mΩ 2.2 W
40367057 10 - 14 A 35 A 16 A 11.2 mΩ 2.2 W
40367058 13 - 19 A 50 A 20 A 6.3 mΩ 2.3 W
40367060 18 - 25 A 63 A 25 A 4.7 mΩ 2.9 W
40367061 24 - 32 A 80 A 32 A 3.2 mΩ 3.3 W

Triggering characteristics:
Kennlinie


Functional description:

This thermic overload relay monitors the motor coil temperature indirectly via the current in the supply line. A dedicated bi-metal element with heating coil is provided for each conducting line to the motor. When the power consumption of the motor exceed the set limit for a certain period of time, the heat will cause the bi-metal element to change shape. The bi-metal element will then break contact 95-96, thus interrupting the control circuit of the motor. Additional mechanical elements trigger quickly in case of a phase drop-out. With the right type of relay and proper settings the motor will be well protected from overload, failure to start and phase drop-out.


Warning:

Terminal screws which are not sufficiently tightened may cause excessive over-heating. The relays must only be conected by specialists. Do not touch live parts !

Setting to rated current bof the motor:

The relay is set to rated current of the motor by rotating the knob ➀ until setting scale with the desired rated current correspods to the arrowhead ➈.

Changing from manual to automatic reset:

Reset button ➁ in position of arrow:

Aut = automatic reset

Man = manual rest by means of button ➂

Function of the blue button:

Button ➂ in position of arrow:

R = reset only

R O = reset and switching off for special applications, e.g. by motor starters and contactor combinations

By operation of the button ➂ in position of arow R O contact 95-96 closes..

Test before commissioning:

Press reset- and switch off button ➂ for resetting of relay. By pressing the bar ➃ into direction of arrow, the relay trips. Break contact 95-96 pens and make contact 97-98 closes. Red contact position indicator ➉ indicates off position.

Auxiliary contacts:

Break contact 95-96 and make contact 97-98 are galnaically separated. Short circuit protection of the auxiliary contacts: 6 A gl. Signalling units can be operated by the aux. contact 97-98. A sigle-circuit changeover contact can be obtained by bridging terminal 95 and 97.