Utilization categories for alternating voltage - KLINGER BORN

Skip Navigation

Choose language

Utilization categories for contactors according to IEC/EN60947-4-1

Type of current Utilization category Typical application
Alternating current AC-1 Non-inductive or low-inductive load, resistance furnaces
  AC-2 Slipring motors: starting, switching off
  AC-3 Suirrelcage motors: starting, switching off while running
  AC-4 Squirrel-cage motors: starting, regenerative braking, reversing, jogging
  AC-5a Switching gas discharge lamps
  AC-5b Switching of incandescent lamps
  AC-6a Switching of transformers
  AC-6b Switching of capacitor banks
  AC-8a Switching hermetically sealed cooling compressor motors with manual reset of the overload release
  AC-8b Switching hermetically sealed cooling compressor motors with automatic reset of the overload release
Direct current DC-1 Non-inductive or low-inductive load, resistance furnaces
  DC-3 Shunt motors: Starting, braking by reversal, inching, dynamic braking of DC motors
  DC-5 Seriers motors: Starting, braking by reversal, inching, dynamic braking of DC motors
  DC-6 Switching of incandescent lamps

Utilization categories for auxilliary contactors according to IEC/EN60947-5-1

Type of current Utilization category Typical application
Alternating current AC-12 Controlling ohmic and inductive loads when isolation through optocouplers is used
  AC-13 Controlling semiconductor loads when isolation through transformers is used
  AC-14 Controlling small electromagnetic loads (≤ 72 VA)
  AC-15 Controlling small electromagnetic loads (≥ 72 VA)
Direct current DC-12 Controlling ohmic and electronic loads when isolation through optocouplers is used
  DC-13 Controlling DC electromagnets
  DC-14 Controlling electromagnetic loads with built-in economy resistors

Utilization categories for load switch, disconnector, circuir breaker and Switching-safets-units according to IEC947-3, EN60947, DIN VDE0660 part 107

Type of current Utilization category Typical application
Alternating current AC-20A(B) 1) Making and breaking without load
  AC-21A(B) 1) Switching of ohmic loads, including small overloads
  AC-22A(B) 1) Switching of mixed ohmic and inductive loads, including small overloads
  AC-23A(B) 1) Switchung of motors or other high-inductive loads
Direct current DC-20A(B) 1) Making and breaking without load
  DC-21A(B) 1) Switching of ohmischer Last einschließlich geringer Überlast
  DC-22A(B) 1) Switching of gemischter ohmischer und induktiver Last einschließlich geringer Überlast (z.B. Nebenschluss-Motoren)
  DC-23A(B) 1) Switching of Motoren oder anderer hochinduktiver Last (z.B. Reihenschluss-Motoren)

1) A: frequent actuation, B: casual actuation

All the switchgears in our range are designed in accordance with VDE0660 for the utilization category AC-3. For the permissiböe power data, please see the respective options.