3-phase 400V starter with Dahlander switching up to 5.5kW - Optional up to 7.5kW
with undervoltage release, overload protection, emergency stop, control voltage 230V
Item No. 0098.4085
Change of switching function with bridge in terminal block X2
- with bridge: switching without triggering the undervoltage release
- without bridge: switching with triggering of the undervoltage release
Setting for the built-in overload protection:
(Overload protection setting = motor rated current × 0.58)
Motor rated current 6.0-8.3 A = setting 3.5-4.8 A
Motor rated current 7.8-10.9 A = setting 4.5-6.3 A
Motor rated current 9.5-12.0 A = Setting 5.5-7.5 A (*)
Motor rated current 12.4-17.2 A = Setting 7.2-10.0 A
(*) Standard equipment
Versions
| Item No. | Delivery Time | Stock | Quantities / Prices |
|---|---|---|---|
| 0098.4085 | 3 Tag(e) | 2 | 212,64 € netto |
Technical Features
Series Specifications
Individual Parameters
Start-up
Direct starter - Dahlander
Switching power max.
7.5kW 400V~/AC-3
Yes
16.0 A
Control voltage
230V/50Hz
electronic brake
No
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58 - Please specify the motor rated current at the end of the ordering process.
Main switch
No
start-stop keyboard
green-red with protective cap
Emergency stop
Yes
Pole switch
Δ / YY
Network connection
3m power cable H07RN-F 5G1.5 with mounted CEE plug 3P+N+E 400V/16A with phase inverter
Motor connection
1.5m motor cable H07RN-F 7G1.5
Housing
K4000
Housing dimensions (LxWxH)
240 x 190 x 128 mm
Mounting
5.3mm through holes 152x223mm and M5 threaded inserts 94x200mm
degree of protection
IP54 (IP65 on request)
Weight
3,256 kg
Hersteller
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach