ABB soft starter 11kW 25A; Type: PSR25-600-70
Us: 100...240V, 50-60Hz
Item No. 4036.6306
The Alternative to Star-Delta Starters
The PSR series includes the most compact soft starters, enabling the design of compact starting devices. The system concept with motor protection circuit breakers and the products of the PSR series provides a significantly more compact starting device than, for example, a star-delta starter.
Features
- Large rated operational voltage range 208-600V AC
- Rated control supply voltage 100-240V AC or 24V AC/DC
- Rated operational current 3-105A
- Large operating ambient temperature range, -25 to +60°C
- Integrated bypass in all sizes saves energy and reduces installation time
- Potentiometer adjustment
- Relay for "Run" signal on all devices
- Relay for "TOR" signal on Type PSR25 ...PSR105
- Optional: Fieldbus communication with Profibus, Modbus, DeviceNet, or CANopen
- Mounting on DIN rail for Type PSR3...PSR45
- Screw mounting for all sizes
- Connection adapter for easy connection with ABB motor protection circuit breaker
- Sophisticated algorithm to eliminate the DC component ensures outstanding starting performance
- For information on soft starters for scroll compressors, see the Softstarter PSRC tab
Versions
Item No. | Manufacturer ID | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|---|
4036.6306 | 1SFA896108R7000 | 1 day(s) | 13 |
Technical Features
Series Specifications
Rated insulation voltage Ui
600V
Rated operating voltage Ue
208...600V +10%/-15% 50/60Hz 5%
Supply voltage Us
100...240V AC 50/60Hz +5% (24V AC/DC +10%/-15% on request)
Power consumption supply circuit
12VA at AC / 5W at 24V DC
Number of event occurrences / hr.
10, further details see "Event processes, connections and protection class" at the end of the table
Ambient temperature
-25...+60°C
Storage temperature
-40...+70°C
LED display
2 pieces for ON/Ready and RUN/TOR
Ramp times
1-20s start / 0-20s stop
Signal relay
240V AC, 3A/24V DC 3A resistive load 240V AC, 0.5A/24V DC, 0.5A AC-15 load (contactors)
Individual Parameters
Type
PSR25-600-70
Power (up to)
11 kW
Motor current
25 A
Control signal
230V
Manufacturer
ABB STOTZ-KONTAKT GmbH, Eppelheimerstr. 82, DE - 69123 Heidelberg
Downloads
Downloads for the Series
Wiring diagrams Technical data sheets Approvals Installation wall mounting Installation instructions Dimension drawing Manual Safety information SettingFunction description and settings
Functional Description
Asynchronous motors are often started directly or with a star-delta circuit. During direct start, extremely high start-up currents occur, up to seven times the rated motor current. The star-delta circuit mitigates the problem by providing a root-3 lower phase voltage. However, switching from star to delta also produces a significant current spike. These starting methods can overload the network, disturb other consumers, cause mechanical problems, and expose the entire drive to high wear.
The solution to these problems is a soft starter. During start-up, the starter reduces the voltage in two of the three phases using phase control. During the adjustable start-up time, the torque increases slowly until full line voltage is applied to the motor. This results in a network and drive-friendly, jerk-free ramp-up of your drive.
The PSR series includes the most compact soft starters, allowing for the design of compact starting devices. The system concept with motor protection switches and the products from the PSR series provides a significantly more compact starting solution than, for example, a star-delta starter.
Integrated bypass relays reduce energy losses and simplify the connection; the setup is incredibly easy thanks to the restrictions to only three potentiometers. The optimized ramp characteristics ensure very smooth acceleration and deceleration under all operating conditions.
Settings - see image under Downloads
1 = Start 1...20s
2 = Deceleration 0...20s - including step voltage
Step voltage = decrease by 2% for each second of increased stop ramp
Stop ramp: 10s -> Step voltage 80% (20% reduction)
3 = Uini = 40...70% results in final voltage 30...60%