Automatic star-delta starter 18.5kW 400V/AC-3 40A
with under-voltage release, overload protection, and main switch
Item No. 0098.4024
Setting for the built-in overload protection:
(setting values for overload protection = rated motor current x 0.58)
Rated motor current 30.2-37.0A = setting 17.5-21.5A
Motor rated current 36.2-43.1A = setting 21-25A (*)
(*) Fitted as standard
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.4024 | 3 day(s) | 4 | 392,54 € Net |
Technical Features
Series Specifications
Star-delta conversion
Automatic
Network form
3-phase 400V
Housing color
gray
Individual Parameters
Switching power
18.5kW 400V~/AC-3
Under-voltage release
230V/50Hz
Yes
40 A
Star-delta conversion
Automatically with adjustable ramp-up time KLIBO star-delta timer
Max. rated motor current
40 A
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58
Note on motor
The motor must be suitable for a 400V delta connection.
electronic brake
No
Main switch
Yes
Emergency stop
No
L-0-R switching
No
Network connection
WAGO spring clamp terminals 10mm² and cable gland M25, clamping range: 11-17mm
Motor connection
WAGO spring clamp terminals 6mm² and cable gland M25, clamping range: 11-17mm
Limit switch connection possible
Yes
Note
WAGO spring clamp terminals 2.5mm² and M16 blind plugs
Enclosure
KB44219
Housing dimensions (LxWxH)
315 x 235 x 187 mm
Mounting dimension
250 x 170
protection type
IP54
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach