Automatic star-delta starter 18.5kW 400V/AC-3 40A
with under-voltage release, overload protection, and main switch
Item No. 0098.4024
Special Features
- Inrush current limiting when starting asynchronous motors
- Reduction of the starting current to one-third of the value during direct starting
- Optimal, operator-independent ramp-up time for your application
- Drive- and grid-friendly starting
- Various designs available
- Control panel can be placed externally
Automatic star-delta starters are used for asynchronous motors from 4 kW to prevent unacceptably high starting currents during startup. The advantage over manually operated star-delta starters is that these starters feature control logic or can be manually actuated, allowing the ramp-up time to be optimally adjusted to the specific application.
The starting process is implemented with a contactor control, a special time relay (KLIBO Star-Delta Timer), and an integrated overload relay. By adhering to important switching sequences and locking of the control, high operational safety is achieved.
The switching time should be set so that when switching from star to delta, at least 80% of the rated speed is reached. A motor suitable for star-delta starting must have a voltage output of 380V / 660V at a line voltage of 380V or delta 380V. For connection, motors with 6 lead-out winding ends are required.
These star-delta starters are used in machine tools, woodworking machines, compressors, and much more. Furthermore, these starters can also be implemented with our new brake controls.
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.4024 | 3 day(s) | 4 |
Technical Features
Series Specifications
Star-delta conversion
Automatic
Network form
3-phase 400V
Housing color
gray
Individual Parameters
Switching power
18.5kW 400V~/AC-3
Under-voltage release
230V/50Hz
Yes
40 A
Star-delta conversion
Automatically with adjustable ramp-up time KLIBO star-delta timer
Max. rated motor current
40 A
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58
Note on motor
The motor must be suitable for a 400V delta connection.
electronic brake
No
Main switch
Yes
Emergency stop
No
L-0-R switching
No
Network connection
WAGO spring clamp terminals 10mm² and cable gland M25, clamping range: 11-17mm
Motor connection
WAGO spring clamp terminals 6mm² and cable gland M25, clamping range: 11-17mm
Limit switch connection possible
Yes
Note
WAGO spring clamp terminals 2.5mm² and M16 blind plugs
Enclosure
KB44219
Housing dimensions (LxWxH)
315 x 235 x 187 mm
Mounting dimension
250 x 170
protection type
IP54
Manufacturer