Star-delta starter 7.5kW 400V/AC-3 16.0A
manually actuated, with undervoltage release, overload protection, and emergency stop.
Item No. 0098.3500
Features
- Power range: 4.0 - 9.0 kW - Higher powers on request
- Inrush current limitation when starting asynchronous motors
- Reduction of inrush current to 1/3 of the value during direct starting, considering the acceleration time
- Various designs available
- Manual operation
Star-delta starters are used for asynchronous motors starting at 4 kW to prevent excessively high inrush currents during startup. The limit values are usually set by the utility companies.
The simplest design of a star-delta switching is realized with a cam switch. The switching from 0 to star and to delta is done manually by the operator. To avoid unwanted voltage spikes, at least 80% of the nominal speed must be reached when switching from star to delta. When connecting the motor, care must be taken to ensure the suitable motor nominal voltage.
A motor suitable for star-delta starting must have a voltage output of 380V / 660V or delta 380V at a mains voltage of 380V. For connection, motors with 6 outgoing winding ends are required.
These star-delta starters are equipped with overload protection. This is wired in series. For the design of the overload protection, the motor nominal current must therefore be multiplied by 0.58. A motor nominal current of, for example, 16A results in a setting value for the overload protection of 9.28A.
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.3500 | 3 day(s) | 38 |
Technical Features
Series Specifications
Star-delta transformation
Manually operated
Network shape
3-phase 400V
Case color
gray
Individual Parameters
Switching power
7.5kW 400V~/AC-3
Under-voltage release Uc
400V/50Hz
Yes
16 A
Max. rated motor current
16 A
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58 - Please specify motor rated current at the end of the ordering process.
Note on motor
Motor must be suitable for 400V delta connection.
electronic brake
No
Main switch
No
Emergency stop
Yes
L-0-R switching
No
Network connection
CEE collar plug 400V 16A 3P+N+E with phase inverter
Motor connection
1m S07RN-F 7G 1.5 with M6 cable lugs
Limit switch connection possible
No
Housing
K3500
Case dimensions (LxWxH)
200 x 140 x 112 mm
Mounting dimensions
4x threaded inserts for screws M5, 118x174mm and 5.3 clearance holes 102x183mm
Degree of protection
IP54
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach