Star-delta starter 7.5kW 400V/AC-3 16.0A
manually actuated, with undervoltage release, overload protection, and emergency stop.
Item No. 0098.3500
Setting for the built-in overload protection:
(setting values for overload protection = rated motor current x 0.58)
Rated motor current 6.0-8.3A = setting 3.5-4.8A
Rated motor current 7.8-10.9A = setting 4.5-6.3A
Rated motor current 9.5-12.0A = setting 5.5-7.5A
Rated motor current 12.4-17.2A = setting 7.2-10.0A (*)
(*) Fitted as standard
Versions
| Item No. | Delivery Time | Stock | Quantities / Prices |
|---|---|---|---|
| 0098.3500 | 3 day(s) | > 5 | 173,79 € Net |
Technical Features
Series Specifications
Star-delta transformation
Manually operated
Network shape
3-phase 400V
Case color
gray
Individual Parameters
Switching power
7.5kW 400V~/AC-3
Under-voltage release Uc
400V/50Hz
Yes
16 A
Max. rated motor current
16 A
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58 - Please specify motor rated current at the end of the ordering process.
Note on motor
Motor must be suitable for 400V delta connection.
electronic brake
No
Main switch
No
Emergency stop
Yes
L-0-R switching
No
Network connection
CEE collar plug 400V 16A 3P+N+E with phase inverter
Motor connection
1m S07RN-F 7G 1.5 with M6 cable lugs
Limit switch connection possible
No
Housing
K3500
Case dimensions (LxWxH)
200 x 140 x 112 mm
Mounting dimensions
4x threaded inserts for screws M5, 118x174mm and 5.3 clearance holes 102x183mm
Degree of protection
IP54
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach