Star-delta starter 7.5kW 400V/AC-3 20.0A
manually operated, with undervoltage trigger, overload protection, main switch, and emergency stop
Item No. 0098.4001
Setting for the built-in overload protection:
(setting values for overload protection = rated motor current x 0.58)
Rated motor current 6.0-8.3 = setting 3.5-4.8A
Rated motor current 7.8-10.9 = setting 4.5-6.3A
Rated motor current 9.5-12.0 = setting 5.5-7.5A
Rated motor current 12.4-17.2 = setting 7.2-10.0A (*)
Rated motor current 15.5-21.5 = setting 9.0-12.5A
(*) Fitted as standard
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.4001 | 3 day(s) | 12 | 195,48 € Net |
Technical Features
Series Specifications
Star-delta transformation
Manually operated
Network shape
3-phase 400V
Case color
gray
Individual Parameters
Switching power
7.5kW 400V~/AC-3
Under-voltage release Uc
400V/50Hz
Yes
20 A
Max. rated motor current
19 A
Overload protection
Yes, adjustable
Setting overload protection
Motor rated current x 0.58 - Please specify the motor rated current at the end of the ordering process.
Note on motor
The motor must be suitable for a 400V delta connection.
electronic brake
No
Main switch
Yes
Emergency stop
Yes
L-0-R switching
No
Network connection
Cable gland M20, clamping range: 10-14mm and 4mm² terminal blocks.
Motor connection
Cable gland M20, clamping range: 10-14mm and 4mm² terminal blocks.
Limit switch connection possible
Yes, 400V
Note
for 400V, connection to 4mm² terminal blocks.
Housing
K4000
Case dimensions (LxWxH)
240 x 190 x 128 mm
Mounting dimensions
5.3mm through holes 152x223mm and M5 threaded inserts 94x200mm
Degree of protection
IP54
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach