Starter K3000 3Ph-400V
with undervoltage release 230V, emergency stop and electronic brake, thermal contact connection possible
Item No. 0098.3015
Under-voltage release according to IEC 204-1, EN 60204, VDE 0113, section 7.5, for protection against automatic restart after voltage dip and voltage recovery
Versions
| Item No. | Delivery Time | Stock | Quantities / Prices |
|---|---|---|---|
| 0098.3015 | 1 Tag(e) | > 5 | 100,90 € netto |
Technical Features
Series Specifications
Startup
Direct startup
Rated operating voltage Ue
400V/50Hz
Rated operating current Ie
16A
Connection
3-phase 400V
Keypad
with protective cap
Pre-insurance
16A gL/gG
Installation position
Arbitrary
Ambient temperature
-10°C...+40°C
protection class
Enclosure IP54 (Higher protection class on request)
Impact resistance
IK08
Conformity
CE
Individual Parameters
Switching power
7.5kW 400V~/AC-3
contactor
Klibo7.5
With shock attachment (protection against unintentional starting after a voltage drop)
No
Network input
CEE collar plug 3P+N+E 16A 400V with phase inverter
Motor connection
1m H07RN-F 5G 1.5 thermal contact connection possible (potential-free, no PTC)
additional line input
No
Type of operation
Push buttons On/Off + Emergency Stop
Actuation
electrically on/electrically off
Switching functions
0-1 and emergency stop
switching frequency
20/h at 10A braking current
Undervoltage release Uc
230V/50-60Hz
Control circuit fuse
No
electronic brake
Yes
Maximum braking current
16 A
Circuit for mechanical brake
No
Overload protection
No
Emergency stop
Yes
Rotary field detection
No
Pole switch
No
Limit switch connection possible
No
Mounting dimension
68x68mm
Mounting tabs
No
Weight approx.
1,204 kg
Hersteller
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach
Downloads
Dimension drawing
Circuit diagram
Safety information
Instructions for adjusting the braking current [EN]