Starter K3000 3Ph-400V
with undervoltage release, overload protection, electronic brake, and emergency stop, thermocontact connection possible, for external start-stop.
Item No. 0099.0663
Undervoltage release in accordance with IEC204-1, EN60204, VDE0113, section 7.5, for protection against automatic restart after voltage dip and voltage recovery
3m control cable A07RN-F 3x1.5 for connecting an external start-stop / emergency stop switch unit
Versions
| Item No. | Delivery Time | Stock | Quantities / Prices |
|---|---|---|---|
| 0099.0663 | 1 day(s) | > 5 | 126,54 € Net |
Technical Features
Series Specifications
Startup
Direct startup
Rated operating voltage Ue
400V/50Hz
Rated operating current Ie
16A
Connection
3-phase 400V
Type of actuation
Push buttons On/Off
Keypad
with protective cap
Installation position
Arbitrary
Mounting dimension
68x68mm or with mounting tabs
Switching functions
0-1
Pre-insurance
16A gL/gG
Ambient temperature
-10°C...+40°C
Enclosure material
ABS gray or yellow
Impact resistance
IK08
Material collar plug
PA6 red
Degree of protection
IP54
Conformity
CE
Individual Parameters
Network input
3m H07RN-F 5G 1.5 with CEE plug 3P+N+E 400V / 16A with phase changer
Motor connection
2m H07RN-F 7G1.5 with connection option for a thermal contact, neutral conductor included (floating potential, no PTC)
Undervoltage release Uc
230V/50Hz
electronic brake
Yes
Maximum braking current
16 A
Circuit for mechanical brake
No
Overload protection
Yes
Setting overload protection
1.6...16A, fixed setting t - Please specify the motor rated current at the end of the ordering process.
Emergency stop
No
Rotary field detection
No
Pole switch
No
Limit switch connection possible
No
Actuation
electric On/mechanical Off
Fastening
87x194mm
Mounting tabs
Yes
switching frequency
20/h at 10A braking current
degree of protection
IP55
Weight
2.65 kg
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach
Downloads
Dimension drawing
Circuit diagrams
Safety information