Starter K400 1Ph-230V
with undervoltage release, thermocontact connection possible
Item No. 0098.4000
Features
- With undervoltage release (standard) to protect against automatic restart after voltage drop and voltage restoration
- Available with electronic brake
- Available with integrated overload protection
Please note that the following versions are example configurations. Due to the many combinations of individual components, we are able to produce a wide variety of models. If the desired configuration is not included in these versions, please contact us.
Note on plug orientation and cable outlet:
Plug orientation and cable outlet refer to the control panel. The control panel always points to 6 o'clock, see illustration under "Further Views and Drawings". The left cable outlets are only possible without overload protection. Further cable outlets available upon request.
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.4000 | 1 day(s) | 6 |
Technical Features
Series Specifications
Start-up
Direct start
Rated operating voltage Ue
230V/50Hz
rated switching capacity
3.0kW 230V~
Rated operating current Ie
13.5A
Connection
1Ph-230V
Contactor
KB-04
Network input
Network cable
Actuation type
Push buttons On/Off
Keypad
with protective cap
Installation position
Any, except keyboard up
Fixing dimension
68x68mm
Switching functions
0-1
Switching frequency
60/h
Pre-insurance
16A gL/gG
ambient temperature
-10°C...+40°C
Housing material
ABS black or yellow
degree of protection
IP54
Conformity
CE
Individual Parameters
Network input
2m H07RN-F3G 1.5 with protective contact plug
Motor connection
1m H07RN-F 4G 1.5 thermocontact connection possible (isolated, no PTC)
Under-voltage release Uc
230V/50Hz
electronic brake
No
Overload protection
No
Actuation
mechanical On/Off
Switching frequency
60/h
Weight
0.5 kg
Manufacturer
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach
Downloads
Dimension drawing Circuit diagram Safety information