Universal switch K3500 for 1Ph-110-240V and 3Ph-380-440V-50-60Hz
with undervoltage release, main switch, and emergency stop
Item No. 0098.0022
Undervoltage release according to IEC 204-1, EN 60204, VDE 0113, section 7.5, for protection against automatic restart after voltage dip and voltage recovery
for 1Ph 110-240V / 4kW / 50-60Hz and 3Ph 380V-440V / 7.5kW / 50-60Hz
Versions
| Item No. | Delivery Time | Stock | Quantities / Prices |
|---|---|---|---|
| 0098.0022 | 1 Tag(e) | 4 | 163,90 € netto |
Technical Features
Series Specifications
Start-up
Direct start
Connection
3-phase 400V
Undervoltage release Uc
230V/50Hz or 400V/50Hz
Individual Parameters
Switching power
1Ph: 4kW / 50-60Hz / 3Ph: 7.5kW / 50-60Hz
Under-voltage release Uc
100-250V / 50-60Hz
rated operational current Ie
16.0A
Actuation
Electric On/Off
Network input
Connections via spring clamp terminals 2.5mm², cable gland M20, clamping range 5.0-12mm.
Motor connection
Connections via spring-loaded terminals 2.5mm², cable gland M20, clamping range 5.0-12mm
electronic brake
No
Overload protection
No
Emergency stop
Yes
Main switch
Yes
Operating lights
Operational lights green (control switched on)
Isolation transformer
No
Housing
K3500
Dimensions (LxWxH)
200x140x112 mm
Fastening
M5 blind holes 118x174mm and 5.3 passing holes 102x183mm
Degree of protection
IP54
Weight
1.44 kg
Hersteller
Klinger & Born GmbH, In den Schlangenäckern 5, DE - 64395 Brensbach