Overload protection Klibo Mxx,xA
The optimal protection for your engine.

Description
Features
- Cost-effective
- Compact design
- Safe and simple operation
- Very good price-performance ratio
- Individual customization according to specific customer requests possible
- Short delivery time due to in-house production
- Motor protection according to IEC204-1, EN60204-1, DIN VDE0113 Part 1 / IEC947-4-1, EN60947-4-1, DIN VDE0660 Part 102
Release characteristic see "More Images"
Series Specifications
Field
0.6...16.0 A
Adjustment
Factory setting (according to nominal current specification)
Explanations
1-pole, 2-pole, 3-pole
Mode of operation
Thermal bimetal, activation via microswitch.
Ue
400 V
UI
400 V
switching voltage
Max. 400V~
Switching power of the relay
2(0.5)A 250V~
Restoration
Automatic
Trigger class
10 A
B10 (B10d)
1,000,000 (1,500,000)
Design form
Insert
Housing material
PA6.6 V-0
Recommended overcurrent protection (at 400V) for rated current 0.16 - 0.60A
4 A
Recommended pre-fuse (at 400V) for rated current 0.60 - 1.00A
6 A
Recommended pre-fuse (at 400V) for rated current 1.00 - 1.60A
10 A
Recommended pre-fuse (at 400V) for rated current 1.60 - 16.0A
16 A
Trip characteristic Ie x 1.05
Trigger time t>2h
Release characteristic Ie x 1.20
Trigger time t<2h
Trigger characteristic Ie x 1.50
Trigger time t<2min