Starter K900 3Ph-400V
with undervoltage trigger, thermal contact connection possible
Item No. 0098.9030
Undervoltage release in accordance with IEC204-1, EN60204, VDE0113, section 7.5, for protection against automatic restart after voltage dip and voltage recovery
Versions
Item No. | Delivery Time | Stock | Quantities / Prices |
---|---|---|---|
0098.9030 | 1 day(s) | 3 |
Technical Features
Series Specifications
Start-up
Direct start
Rated operating voltage Ue
400V/50Hz
Rated switching capacity AC-3
4.0kW 400V~
rated operating current Ie
9.0A
Connection
3-phase 400V
contactor
KB-04
Network input
CEE collar plug or power cable
Actuation type
Push buttons On/Off
Button panel
with protective cap
Installation position
Any, except keyboard up.
Mounting dimension
68x68mm
switching functions
0-1
Pre-coverage
16A gL/gG
Ambient temperature
-10°C...+40°C
Housing material
PP black
Material collar plug
PA6 red
Protection class
IP54
Conformity
CE
Individual Parameters
Network input
CEE collar plug 3P+N+E 16A 400V with phase changer
Motor connection
Motor assembly, thermal contact connection possible (potential-free, no PTC)
Under-voltage release Uc
400V/50Hz
Actuation
mechanical on/off
electronic brake
No
Wiring for mechanical brake
No
Overload protection
No
Switching frequency
60/h
Weight approx.
0.414 kg
Manufacturer